Fa'ata'ita'iga
GPVN -12Kv/17.5kV I totonu AC Maualuluga Voltage Vacuum vacuum breaker
Fa'amatalaga Fa'apitoa
Leai. | Aitema | Vaega | Fa'amaumauga | ||||||
1 | Fuafuaina voltage | kV | 7.2~12(15/17.5) | ||||||
2 | Fa'atatau taimi | Hz | 50/60 | ||||||
3 | Fa'atatau i le taimi nei | A | 630,1000,1250 | 1600 | 2000,2500,3150 | 4000 | |||
4 | Fa'atatauina le la'au fa'ato'a fa'asa'o | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
5 | Fa'avasegaina fa'aa'au fa'a'a'ai pu'upu'u | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
6 | Fa'atatauina mo se taimi pupuu e tetee atu i le taimi nei | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
7 | Fa'atatau pito maualuga e tetee atu i le taimi nei | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
8 | Fuafuaina toso i fafo motusia le taimi nei | kA | 12.6 | 12.6 | 16 | 16 | 20 | ||
9 | Fa'avasegaina i fafo-o-le-vase fa'alelalo fa'aletonu le taimi nei | kA | 17.4 | 21.7 | 27.4 | 27.4 | 34.7 | 34.7 | 43.5 |
10 | Fa'avasegaina le va'aiga pupuu taimi ta'i | Taimi | 50 | 30 | 30 | 12 | |||
11 | Fa'asologa o galuega fa'atatau | O-0.3s-CO-180s-CO | O-180s-CO-180s-CO | ||||||
12 | Fa'atatauina gau o le taimi nei o le tasi faletupe capacitor | A | 630 | ||||||
13 | Fuafuaina gau o le taimi nei o tua i tua capacitor faletupe | A | 400 | ||||||
14 | 1min.Malosi'i taimi e fa'asagatau volt | kV | Laasaga i lea vaega/i le lalolagi: 42, i luga o fesootaiga matala:48 | ||||||
15 | O le uila e tetee atu i le voltage | kV | Laasaga i lea vaega/i le lalolagi: 75, i luga o feso'ota'iga tatala:85 | ||||||
16 | Ola fa'ainisinia | Taimi | 20000 | ||||||
17 | Taimi tapunia | ms | ≤75 | ||||||
18 | Taimi tatala | ms | ≤60 | ||||||
19 | Taimi e teu ai le mana i lalo ole voltage fa'atatau | s | ≤10 |
Otootoga o le GPVN-12E
GPVN-24□ Vacuum Circuit Circuit Breaker AC High Voltage i totonu
Fa'amatalaga Fa'apitoa
Leai. | Aitema | Vaega | Fa'amaumauga | |||
1 | Fuafuaina voltage | kV | 24 | |||
2 | Fa'atatau taimi | Hz | 50/60 | |||
3 | Fa'atatau i le taimi nei | A | 630 1250 1600 2000 2500 3150 4000 | |||
4 | Fa'atatauina le la'au fa'ato'a fa'asa'o | kA | 20 | 25 | 31.5 | 31.5 |
5 | Fa'avasegaina fa'aa'au fa'a'a'ai pu'upu'u | kA | 50 | 63 | 80 | 80 |
6 | Fa'atatauga pupuu fa'asagatau i le taimi nei(4s) | kA | 20 | 25 | 31.5 | 31.5 |
7 | Fa'atatau pito maualuga e tetee atu i le taimi nei | kA | 50 | 63 | 80 | 80 |
8 | Fa'avasegaina i fafo o le la'asaga soli o le taimi nei | kA |
|
| 12.6 | 12.6 |
9 | Fa'atatauina le ta'atiaga o le fa'aletonu o le eleele | kA | 17.4 | 21.7 | 27.4 | 27.4 |
10 | Fa'avasegaina taimi ta'atia o le a'oga fa'a-pu'upu'u | Taimi | 50 | |||
11 | Fa'ailoga fa'asologa fa'agaioiga |
| O-0.3s-CO-180s-CO | |||
12 | Fa'atatauina gau o le taimi nei o le tasi faletupe capacitor | A | 630 | |||
13 | Fa'atatauina le gau o le taimi nei o tua-i-tuai capacitor faletupe | A | 400 | |||
14 | 1min.Malosi'i taimi e fa'asagatau volt | kV | 50 | |||
15 | O le uila e tetee atu i le voltage | kV | 125 | |||
16 | Ola fa'ainisinia | Taimi | 20000 | |||
17 | Taimi tapunia | ms | 75 | |||
18 | Taimi tatala | ms | 60 | |||
19 | Taimi e teu ai i lalo ole fua fa'atatau | s | 10 |